Community Charge Kiosk — Solar Edition (24 V → USB-C PD ×4 + Qi + 12 V)
SOLAR24 V DCUSB-C PD

Community Charge Kiosk — Solar Edition

PV → MPPT → 24 V bus → 4× USB-C PD (100 W), 2× Qi pads, 2× 12 V sockets, optional queue screen. Field-deployable; serviceable with basic tools.

What changes vs. the base kiosk

  • Built-in **PV subsystem**: folding/rigid panels → **combiner** (fused) → **MPPT** → 24 V battery bus.
  • Correct **connection order**: Battery → MPPT → PV (reverse to shut down).
  • Charge profile set for **LiFePO₄ 24 V** (8 S): Absorb ≈ 28.4–29.2 V, Float ≤ 27.2 V (or off).

Target solar spec

Array400–800 W (rigid or suitcase)
ControllerMPPT 100/30–100/50 (or 150/35) class
CombinerString fuses/breakers per string
Cabling10 AWG PV cable (MC4), short runs

Bill of Materials — Solar Add-On

PartNotes
PV Panels (400–800 W)Two 200 W “24 V-class” in series (2S) per string; for 800 W use 2S2P
Combiner boxOutdoor-rated; string **fuse holders or breakers**; deadfront cover
Fuses / breakersPer panel datasheet (often **15 A** max-series-fuse); one per string
DisconnectsPV DC disconnect; battery-side breaker on MPPT BAT+
MPPT100 V/30–50 A class (e.g., 100/50) — must fit PV Voc (cold) and array current
PV wire & MC410 AWG PV cable; MC4 branch connectors if paralleling strings
Labels & placards“PV DC”, “BATTERY”, “DISCONNECT” etc.
Re-use from base kioskNotes
24 V battery bus + fuse (Class-T/MRBF)Class-T at source; branch MRBF/ATO as sized
USB-C PD 100 W modules (×4)12–24 V input, PD 3.0; one **10 A** branch fuse each
Qi pads (×2)3–5 A branch fuses; FOD & thermal cutback
12 V sockets (×2)15 A branch fuses, 12 AWG runs
SB50 inlet50 A quick-connect for battery box / alt-power

Size wire by ampacity & drop; fuse **for the wire**, not the load.

Wiring Overview

PV+ (String 1) ─ Fuse ┐ ├─── Combiner ─── PV Disconnect ─── MPPT PV+ PV+ (String 2) ─ Fuse ┘ PV− strings common to Combiner → MPPT PV− MPPT BAT+ ─── Battery-side breaker ─── 24 V Positive Bus (Class-T at battery source) MPPT BAT− ──────────────────────────── 24 V Negative Bus 24 V Bus → Branch fuses → { 4× USB-C PD, 2× Qi pads, 2× 12 V sockets } Returns → Negative Bus → Battery − Order of operations: 1) Connect Battery to MPPT (and close BAT+ breaker) 2) Close PV Disconnect to connect array (Shutdown is reverse: open PV Disconnect first, then BAT+)

Check panel datasheet for **Max Series Fuse** and **Voc**; ensure MPPT **max PV voltage** isn’t exceeded in cold weather.

Step-by-Step Build (Solar path)

  1. Panel layout. For 400 W: use 2× “200 W 24 V-class” in **series** (2S1P). For 800 W: two of those strings in **parallel** (2S2P). Keep strings identical; same orientation/tilt.
  2. Combiner. Mount an outdoor PV combiner. Install **one fuse or breaker per string** sized to the panel’s **Max Series Fuse** (often 15 A). Land positives to fuse holders, negatives to the negative bar.
  3. PV disconnect & run. From combiner, route to a PV DC disconnect, then to the MPPT PV inputs with 10 AWG PV cable. Use strain reliefs and MC4 torque spec.
  4. MPPT battery side. From MPPT BAT+ add a **DC breaker** to the **24 V positive bus**; BAT− to negative bus. Close the **battery main fuse** near the source (Class-T/MRBF per your base box).
  5. Program MPPT for LiFePO₄ 24 V. Absorb ≈ 28.4–29.2 V, Float ≤ 27.2 V (or disabled). No equalize. Temperature compensation usually off for LiFePO₄—follow your battery doc.
  6. Bring up safely. **Battery → MPPT** first, then **PV**. Verify PV Voc < MPPT max, then close PV disconnect. Confirm charge current rises in sun.
  7. Thermals. With 600–800 W PV driving heavy charging plus users on PD/Qi, add a filtered 80 mm fan over PD modules if internal air exceeds 40 °C.
  8. Labeling. Placard combiner, disconnect, MPPT, and bus bars; update your lid quick-start.

String sizing tips

  • Controller must support **PV Voc (cold)** and **array Isc**. Check panel temp-coeff for Voc and site min-temp.
  • Long cable? Up-size wire to reduce voltage drop (especially on PV→MPPT).
  • Parallel strings → fuse/breaker **each string** in combiner.

Hazards

  • PV is a live source in sun. Use the **PV disconnect** before service.
  • DC arcs are spicy. Tighten to torque spec; cover busbars.
  • Battery OCP must be **near the source**; sheath exceptions apply but don’t stretch it.

Harvest & Runtime Estimators

Daily Solar Harvest




Get PSH from NREL PVWatts/NSRDB for your location.

Net Runtime from Battery




× PD @ W
× Qi @ W
W other (router/fan)

Quick-Start (print this for the lid)

  1. Plant panels; plug to **Combiner**; open PV Disconnect.
  2. Battery main fuse **closed** → MPPT **ON**.
  3. Close **PV Disconnect** (sunny? it’ll start charging).
  4. Use ports: 4× USB-C PD (100 W with 5 A e-marked cable), 2× Qi (15–25 W), 12 V sockets (15 A).
  5. Shutdown: open **PV Disconnect** → open MPPT BAT+ breaker → service.

Bill of Materials — Quick List (Solar bits only)

ItemSpecQty
PV panels200 W “24 V-class”; 2 in series per string2–4
CombinerMNPV-class outdoor combiner with fuseholders/breakers1
String fusesPer module spec (often 15 A); one per string2–4
PV disconnect≥ 150 VDC rated switch1
MPPT100/50 (or 150/35) class1
PV cable & MC410 AWG PV wire; MC4 branch sets if 2S2Pas needed
BAT+ breakerOn MPPT output to 24 V bus1
LabelsPV DC / DISCONNECT / BATTERYset

Notes & Rationale

  • Battery first, PV second: protects the MPPT; reverse on shutdown to avoid uncontrolled PV on a sleeping controller.
  • LiFePO₄ setpoints: use 28.4–29.2 V absorb, ≤27.2 V float or disable float for mobile use to reduce idle cycling.
  • String OCP & combiner: when paralleling strings, each string must have its own OCPD in a combiner; follow your module’s “Max Series Fuse.”
  • Wire & fusing: size by ampacity/voltage drop; place source OCP near battery; sheath exceptions allow longer distance but don’t abuse it.
  • Harvest math: Daily Wh ≈ PV_W × PSH × efficiency (≈0.7–0.8 for real life). Use site PSH from NREL.

Sources

  • Victron SmartSolar manuals — battery/PV connection order & MC4 guidance.
  • Battle Born (LiFePO₄) — 24 V charge voltages (absorb/float) and lithium charge basics.
  • MidNite Solar MNPV combiner manuals — per-string fusing/breakers in combiners.
  • Blue Sea Systems — DC ampacity & voltage-drop methods; ABYC E-11 OCP placement summary.
  • NREL PVWatts & Solar Resource/NSRDB — site-specific sun hours and production estimation.
Built for GamerzCrave • Solar upgrade that actually pencils out.
Scroll to Top